Circuit Configuration, Printed Circuit Boards and connector details - Toshiba Split-Type Air Conditioner RAV-SM562UT-E RAV-SM562BT-E
RAV-SM562CT-E - RAV-SM802UT-E RAV-SM802BT-E RAV-SM802CT-E - RAV-SM1102UT-E
RAV-SM1102BT-E RAV-SM1102CT-E - RAV-SM1402UT-E RAV-SM1402BT-E RAV-SM1402CT-E - RAV-SP1102UT-E
Indoor Control CircuitOutline of Main Controls
RAV-SM562AT-E, RAV-SM802AT-E, RAV-SM1102AT-E, RAV-SM1402AT-E
Pulse Motor Valve (P.M.V.) control
1. PMV is controlled with 50 to 500 pulses during operation, respectively.
2. In cooling operation, P.M.V. is controlled with the temperature difference
between TS sensor and TC sensor.
3. In heating operation, P.M.V. is controlled with the temperature difference between TS sensor and TE sensor.
4. For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and heating operations.
5. When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD sensor. The aimed value is usually 105°C for SM562 and 100°C for SM802, SM1102, SM1402 in both cooling and heating operations.
3. In heating operation, P.M.V. is controlled with the temperature difference between TS sensor and TE sensor.
4. For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and heating operations.
5. When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD sensor. The aimed value is usually 105°C for SM562 and 100°C for SM802, SM1102, SM1402 in both cooling and heating operations.
[A sensor trouble may cause a liquid back-flow or abnormal
overheat resulting in excessive shortening of the compressor life. In a case of
trouble on the compressor, be sure to check there is no error in the resistance
value and the refrigerating cycle of each sensor after repair and then start
the operation.]
Discharge temperature
release control
1. This function controls the operation frequency, that is, lowers the operation frequency when the discharge temperature has not lower or the discharge temperature has rapidly risen during P.M.V. control. It subdivides the frequency control up to a unit of 0.6Hz to stabilize the cycle.
2. When the discharge temperature is detected in an abnormal stop zone, the unit stops the compressor and restarts after 2 minutes 30 seconds. The error counter is cleared when it has continued the operation for 10 minutes. If the abnormal stop zone has been detected by 4 times without clearing of counter, an error “P03” is displayed. * The cause is considered as excessively little amount of refrigerant, defective PMV, or cloggiCurrent release control.
1. This function controls the operation frequency, that is, lowers the operation frequency when the discharge temperature has not lower or the discharge temperature has rapidly risen during P.M.V. control. It subdivides the frequency control up to a unit of 0.6Hz to stabilize the cycle.
2. When the discharge temperature is detected in an abnormal stop zone, the unit stops the compressor and restarts after 2 minutes 30 seconds. The error counter is cleared when it has continued the operation for 10 minutes. If the abnormal stop zone has been detected by 4 times without clearing of counter, an error “P03” is displayed. * The cause is considered as excessively little amount of refrigerant, defective PMV, or cloggiCurrent release control.
The output frequency and the output voltage are controlled by AC
current value detected by T02 on the outdoor P.C. board so that input current
of the inverter does not exceed the specified value.ng of cycle.
Current release control
The output frequency and the output voltage are controlled by AC current value detected by T02 on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
The output frequency and the output voltage are controlled by AC current value detected by T02 on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
Cooling fan control
> The outdoor fan is controlled by TE, TD, and TO sensors and also
revolution frequency of the operation. The outdoor is controlled by every 1 tap
of DC fan control (15 taps).
> Only during 60 seconds after the operation has started, the fan is
fixed with the maximum fan tap which corresponds to the zone. After then the fan is controlled by TE sensor
temperature.
> Considering a case that TE sensor has come out of the holder, the
fan is controlled so that revolution frequency of the fan increases regardless
of TE if temperature of TD sensor has risen.
Heating fan control
The outdoor fan is controlled by TE sensor, TO sensor and the
operation frequency. (From Min. W1 to
Max. are controlled)
During 3 minutes after start-up, the fan is fixed with the maximum
fan tap corresponding to zone. After then the fan is controlled by temperature
of TE sensor.
If status, TE > 24°C continues for 5 minutes, the operation
stops. This status is same to the usual Thermo-OFF which has no alarm display,
and the fan restarts after 2 minutes and 30 seconds. This intermittent operation is not abnormal.
and the fan restarts after 2 minutes and 30 seconds. This intermittent operation is not abnormal.
When the above status (2) occurs frequently, it is considered that
the filter of suction part of the indoor unit is stain. Clean the filter and
then restart the operation.
Coil heating control
This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent slackness of the refrigerant inside of the compressor.
This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent slackness of the refrigerant inside of the compressor.
As usual, turn on power of the compressor for the specified time
before a test run after installation, otherwise a trouble of the compressor may
be caused. As same as a test run, it is recommended to turn on power of the
compressor beforehand when starting operation after power of the compressor has
been interrupted for a long time.
A judgement for electricity is performed by TD and TO sensors. If
TO sensor is defective, a backup control is automatically performed by TE
sensor. For a case of defective TO sensor, judge it with the outdoor LED
display.
Coil heating is controlled by TD and TE sensor.
For every model, the power is turned off when TD is 30°C or more.
Defrost control
In heating operation, defrost operation is performed when TE
sensor temperature satisfies any condition in A zone to D zone.
The defrost operation is immediately finished if TE sensor
temperature has become 12°C or more, or it also is finished when condition of
7°C < TE < 12°C has continued for 1 minute. The defrost operation is also
finished when defrost operation has continued for 10 minutes even if TE sensor
temperature has become 7°C or lower.
After defrost operation has finished, the compressor and the
outdoor fan start heating operation after stopped for approx. 50 seconds.
[The minimum TE value between 10 and 15 minutes after heating
operation has started is stored in memory as TE0.]
Board Optional Connector Specifications
Outdoor Controls
Print Circuit Board
P.C. Board Comparison Table for Digital Inverter.
Print Circuit Board
P.C. Board Comparison Table for Digital Inverter.
PRINTED CIRCUIT BOARD [Populated] & Connector Details
Viewed from parts of P.C board - RAV-SM562AT-E,
RAV-SM802AT-E -MCC-5009
RAV-SM1102AT-E, RAV-SM1402AT-E /
RAV-SP562AT-E, RAV-SP802AT-E - MCC-1531
RAV-SP1102AT-E, RAV-SP1402AT-E - MCC-1531
RAV-SM1102AT-E, RAV-SM1402AT-E /
RAV-SP562AT-E, RAV-SP802AT-E, RAV-SP1102AT-E, RAV-SP1402AT-E - IPDU : MCC-1438
CLICK ON THE PICTURES TO ZOOM IN