Fault codes - Condition code and communication code descriptions - ELECTROLUX - KELVINATOR INVERTER SPLIT SYSTEM AC
KSV26CRE - KSV26HRE
KSV35CRE - KSV35HRE
KSV70CRE - KSV70HRE
KSV53HRE
KSV62HRE
KSV80HRE
KSV70CRE - KSV70HRE
KSV53HRE
KSV62HRE
KSV80HRE
Built into the software for model: KSV26HRE & KSV35HRE are two
different diagnostic methods: (Fault Codes & Condition Codes) that can be
used to help diagnose various faults. These two diagnostic types are described.
Note: Where there is a referral to (Remote Control Access – 3)
This indicates the need to use the remote controller to view the relevant fault
code. This is achieved by pressing the “Light” button 3 times within three
seconds.
Note: Where there is a referral to (Remote Control Access – 5)
This indicates the need to use the remote controller to initiate a selected
“Test State”. This is achieved by pressing the “Light” button 5 times within
three seconds.
Fault Code Descriptions
Red LED: Outdoor unit, flashing at 1 hertz.
(Frequency Limit)
(Frequency Limit)
This indicates the compressor has reached its maximum
setting speed.
E4, Indoor Unit.
Yellow LED, Outdoor flashing 7 times.
(Compressor Discharge High Temperature Protection)
Yellow LED, Outdoor flashing 7 times.
(Compressor Discharge High Temperature Protection)
Check the outdoor coil for
airflow obstructions. # Check the outdoor fan motor for correct operation.
E5, Indoor Unit.
Yellow LED, Outdoor flashing 5 times.
(AC Over-Current Protection)
Yellow LED, Outdoor flashing 5 times.
(AC Over-Current Protection)
Check supply voltage.
E8, Indoor Unit. (Delayed)
Yellow LED, Outdoor flashing 6 times.
(Anti-High Temperature Protection)
Yellow LED, Outdoor flashing 6 times.
(Anti-High Temperature Protection)
Check the indoor coil for airflow
obstructions.
Check the indoor fan motor for correct operation.
EE, Indoor unit.
Yellow LED, Outdoor flashing 11 times.
(Loading EEPROM malfunction)
Yellow LED, Outdoor flashing 11 times.
(Loading EEPROM malfunction)
Check if the Program Chip is anchored correctly
to the outdoor PCB.
Note: If the Program Chip is correctly anchored, yet “EE” fault still exists, replace the outdoor PCB assembly.
Note: If the Program Chip is correctly anchored, yet “EE” fault still exists, replace the outdoor PCB assembly.
FO, Indoor unit.
Red LED, Outdoor flashing 9 times.
(System Low on Refrigerant)
Red LED, Outdoor flashing 9 times.
(System Low on Refrigerant)
Check for correct refrigerant charge. # Check for
refrigerant leakage.
LP, Indoor unit.
Yellow LED, Outdoor flashing 16 times.
(Indoor & Outdoor units don’t match)
Yellow LED, Outdoor flashing 16 times.
(Indoor & Outdoor units don’t match)
Check if the Indoor & Outdoor
units are correctly matched.
Note: If the indoor & outdoor units are from two different model types, the LP fault code will be displayed.
Note: If the indoor & outdoor units are from two different model types, the LP fault code will be displayed.
P7, Indoor unit.
(Temperature Sensor Circuit Malfunction)
(Temperature Sensor Circuit Malfunction)
Replace outdoor PCB assembly.
P8, Indoor unit.
(Module High Temperature Protection)
(Module High Temperature Protection)
Replace outdoor PCB assembly.
HC, Indoor unit.
Yellow LED, Outdoor flashing 14 times.
(PFC Protection)
Yellow LED, Outdoor flashing 14 times.
(PFC Protection)
Check supply voltage.
U1, Indoor unit.
(Compressor Phase Circuit Detection)
(Compressor Phase Circuit Detection)
Replace outdoor PCB assembly.
U3, Indoor unit.
(Unstable Supply Voltage)
(Unstable Supply Voltage)
Check supply voltage.
U5, Indoor unit.
(Outdoor Circuit Malfunction)
(Outdoor Circuit Malfunction)
Replace outdoor PCB assembly.
U7, Indoor unit. (4-Way Valve Malfunction)
Check for 240V-AC at
the reversing valve coil.
Check the connecting wire from the reversing valve
coil to the outdoor PCB.
Check for correct operation of the reversing valve
coil assembly.
U9, Indoor unit.
(Zero Crossing Malfunction)
(Zero Crossing Malfunction)
Replace outdoor PCB assembly.
Condition Code Description
E2, Indoor Unit - (Condition Code) {Remote Control Access - 3}
Yellow LED, Outdoor flashing 3 times.
(Anti-Freeze Protection)
Yellow LED, Outdoor flashing 3 times.
(Anti-Freeze Protection)
Check if the filters are blocked on the indoor unit.
Check the refrigerant charge.
Check for blockages within the refrigeration
system.
Check the evaporator fan for correct operation.
FH, Indoor Unit - (Condition Code) {Remote Control Access - 3}
Red LED, Outdoor flashing 4 times.
(Anti-Freeze Limit – Frequency Drop)
Red LED, Outdoor flashing 4 times.
(Anti-Freeze Limit – Frequency Drop)
Check if the filters are blocked on the
indoor unit.
Check the refrigerant charge.
Check for blockages within the
refrigeration system.
Check the evaporator fan for correct operation.
F6, Indoor Unit. - (Condition Code) {Remote Control Access - 3}
Red LED, Outdoor flashing 3 times.
(Anti-High Temperature Protection)
Red LED, Outdoor flashing 3 times.
(Anti-High Temperature Protection)
Check the outdoor coil for airflow
obstructions.
Check the outdoor fan motor for correct operation.
H1, Indoor unit.
Yellow LED, Outdoor flashing 2 times.
(Defrosting)
Yellow LED, Outdoor flashing 2 times.
(Defrosting)
PO, Indoor Unit - (Condition Code) {Remote Control Access - 5}
(Compressor Minimum Frequency - Test State)
(Compressor Minimum Frequency - Test State)
Set remote control: (Cooling
mode: 16ºC – Heating mode: 27ºC)
P1, Indoor Unit - (Condition Code) {Remote Control Access - 5}
(Compressor Rated Frequency - Test State)
(Compressor Rated Frequency - Test State)
Set remote control: (Cooling mode:
18ºC – Heating mode: 29ºC)
P2, Indoor Unit - (Condition Code) {Remote Control Access - 5}
(Compressor Maximum Frequency - Test State)
P2, Indoor Unit - (Condition Code) {Remote Control Access - 5}
(Compressor Maximum Frequency - Test State)
Set remote control: (Cooling
mode: 19ºC – Heating mode: 30ºC)
P3, Indoor Unit - (Condition Code) {Remote Control Access - 5}
(Compressor Medium Frequency - Test State)
P3, Indoor Unit - (Condition Code) {Remote Control Access - 5}
(Compressor Medium Frequency - Test State)
Set remote control: (Cooling mode:
17ºC – Heating mode: 28ºC)
EU, Indoor unit - (Condition Code)
EU, Indoor unit - (Condition Code)
Frequency limit/decrease (high temp
of module)
F8, Indoor Unit. - (Condition Code)
Red LED, Outdoor flashing once.
(Low Voltage Protection)
Check supply voltage.
F9, Indoor Unit. - (Condition Code)
Red LED, Outdoor flashing twice.
(Lack of Refrigerant)
Check refrigerant amount.
PH, Indoor Unit. - (Condition Code)
Yellow LED, Outdoor flashing 13 times.
(High Voltage Protection)
Check supply voltage.
F8, Indoor Unit. - (Condition Code)
Red LED, Outdoor flashing once.
(Low Voltage Protection)
Check supply voltage.
F9, Indoor Unit. - (Condition Code)
Red LED, Outdoor flashing twice.
(Lack of Refrigerant)
Check refrigerant amount.
PH, Indoor Unit. - (Condition Code)
Yellow LED, Outdoor flashing 13 times.
(High Voltage Protection)
Check supply voltage.
PL, Indoor Unit. - (Condition Code)
Yellow LED, Outdoor flashing 12 times.
(Low Voltage Protection)
Check supply voltage.
P5, Indoor Unit - (Condition Code)
(Compressor Current Out of Normal Range)
Check the indoor & outdoor coils for airflow obstructions.
HO, Indoor Unit - (Condition Code)
(Anti-High Temperature Protection, Heating Mode)
Yellow LED, Outdoor flashing 12 times.
(Low Voltage Protection)
Check supply voltage.
P5, Indoor Unit - (Condition Code)
(Compressor Current Out of Normal Range)
Check the indoor & outdoor coils for airflow obstructions.
HO, Indoor Unit - (Condition Code)
(Anti-High Temperature Protection, Heating Mode)
Check the indoor coil for
airflow obstructions. # Check the indoor fan motor for correct operation.
H4, Indoor Unit - (Condition Code)
Yellow LED, Outdoor flashing 6 times.
(Anti-High Temperature Protection)
H4, Indoor Unit - (Condition Code)
Yellow LED, Outdoor flashing 6 times.
(Anti-High Temperature Protection)
Check the indoor & outdoor coils for
airflow obstructions. # Check the indoor & outdoor fan motor for correct
operation.
H5, Indoor Unit - (Condition Code)
Yellow LED, Outdoor flashing 4 times.
(IPM Protection)
H5, Indoor Unit - (Condition Code)
Yellow LED, Outdoor flashing 4 times.
(IPM Protection)
Over current protection of IPM module.
H7, Indoor Unit - (Condition Code)
(IPM Protection)
(IPM Protection)
Over current protection of IPM module.
Communication Fault
If both indoor & outdoor PCB’s appear okay
Disconnect the main power supply to the indoor unit by
means of the isolation switch. After approximately one minute, turn the power
supply back on & attempt to operate the unit in “Auto” mode with a set
temperature of two degrees above or below the ambient temperature.
If the Communication fault has not cleared:
If the Communication fault has not cleared:
Check for supply
voltage at the following points.
• Between the Active -Out & Neutral
points on the indoor PCB.
• Between the Active & Neutral points on the
indoor terminal block.
• Between the Active & Neutral points on the outdoor
terminal block.
• Between the Active & Neutral points on the outdoor PCB.
Note: If all the above checks relating to the supply voltage points have been completed, yet the error code still exists, continue: (Next blog post)
Note: If all the above checks relating to the supply voltage points have been completed, yet the error code still exists, continue: (Next blog post)