Sunday, March 24, 2013

PRECOR TREADMILL - FAULT DISPLAY CODES - REMEDIES - 2 of 2




FAULT DISPLAY CODES                        [2 of 2]


Error 40 - No Lift Motion Detected
Description:  Error indicates that the incline (lift) system on either a treadmill or EFX has been instructed to start moving and no lift motion has been detected by the lift position monitoring system.
Possible Causes
1. The lower PCA lift fuse blown.
2. The lift motor is physically jammed and unable to move.
3. The lower PCA is bad.
4. The lift capacitor is bad.
5. A lift motor winding is bad.
6. The upper PCA to lower PCA interconnect cable is bad.
7. The upper PCA is bad.
Possible Remedies
1. Remove power from the unit and remove the lift fuse from the lower PCA. Measure the fuse with an ohmmeter, the fuse should read approximately 1 ohm or less. If the ohmmeter reading is significantly high, replace the fuse. If the fuse is open, please refer to #3 and #4 below before you continue.
2. Disconnect the lift motor from the lift platform (treadmill) or ramp (EFX). If the lift tube or lift nut is jammed against the motor housing, rotate the lift nut or lift tube away from the motor housing. If the lift was jammed, please refer to #3 below before you continue. Calibrate the lift motor per the appropriate service manual procedure and reattach the lift motor to the lift platform or ramp.
3. The lower PCA can fail in one of two modes. The lift switch could fail in an operated condition. If this happens the lift will move (either up or down) as soon as the unit is powered up. The typical result is that the lift will be physically jammed as described above, it will also probably cause the lift fuse to blow.. The lift switch may also fail in an open condition. If this happens the lift will not operate in one direction. If either of these conditions occur the lower PCA must be replaced.
4. Some units use external lift capacitors, most have the lift capacitor mounted inside the lift motor. This section for for use on units with external lift capacitors. If the lift capacitor is shorted, the lift fuse will blow. The capacitor may be checked for a short by disconnecting it from the lift motor and measuring it with an ohmmeter. A good capacitor will read in the millions of ohms. If the reading insignificantly low, replace the capacitor. Capacitors also fail in the open condition. If a lift capacitor is open the lift motor will try to run but will not have normal power. The capacitor may checked by measuring the A.C voltage across the capacitor. A good capacitor will read A.C. peak voltage an open capacitor will read A.C RMS voltage.
5. If a lift motor winding is bad the lift will not operate in one or both directions depending on the exact fault in the motor. The lift motor winding may be checked with an ohmmeter. A.C lift motors will have a split winding (3 wires) D.C lift motors will have a single winding. On A.C motors both windings must be checked. Depending on the lift motor being tested, normal winding readings could vary anywhere between 1 and 60 ohms. Refer to the appropriate service manual for the motor being tested.
6. Substitute a known good interconnect cable to determine if the existing interconnect cable is bad.
7. Substitute a known good upper PCA to determine if the existing upper PCA is bad.

Error 41 - Lift has not responded in Acceptable Time
Description:  This error code was present in early versions of software and is no longer being used. Should you encounter software with an error 41, troubleshoot it in the same manner as an error 40.

Error 42 - Lift Position Value Out of Range
Description:  This error code monitors the physical lift position via a lift position potentiometer that mechanically tracks the lifts physical position and sends a D.C. voltage back to the control system that is converted to an eight bit digital number. This number is then used to represent the lifts physical position. The software sets upper and lower numerical limits. If the lift position number is found to be outside of the set limits, error 42 will be displayed. When troubleshooting an error 42 is important to be aware of the actual physical position of the lift when the error occurs. If the lift is physically out of range or jammed you must first determine
why the lift is physically out of range. When the lift is out of range the error 42 is a secondary symptom and the problem should treated as an error 40 instead of an error 42.
Possible Cause
1. Bad or intermittent connection in the lift motor connector.
2. The lift motor requires re-calibration.
3. The lift motor potentiometer is bad.
4. The lower PCA to upper PCA interconnect cable is bad.
5. The lower PCA is bad. (This is a rare condition)
6. The upper PCA is bad. (This is a rare condition)
Possible Remedies
1. Intermittent connections can be difficult to locate. If the error 42 conditions are intermittent a connection is almost certainly the problem. This is especially true if the error 42 occurs while the lift is within its normal physical range. Carefully inspect the lift potentiometer connector, repair the poor connection, if possible. If the intermittent connection cannot be found or repaired, replace the lift motor. A lift calibration number of 0 or 255 indicates an open or shorted potentiometer connection. This problem could be anywhere between the lift motor and the upper PCA. It can typically be found and traced with an ohmmeter.
2. Refer to the appropriate service manual lift calibration procedure for the unit being tested. If the lift position number/physical lift position doesn’t correspond with the service manual, re-calibrate the lift motor.
3. If the lift calibration number is not 0 or 255 and does not increment when the lift motor moves, replace the lift motor. A
4. Substitute a known good interconnect cable to determine if the existing interconnect cable is bad.
5. Substitute a known good lower PCA to determine if the existing lower PCA is bad.
6. Substitute a known good upper PCA to determine if the existing upper PCA is bad.

Error 43 - Zero Switch not found
Description:  The C944 and several versions of C96X used a lift position identification system that did not utilize a potentiometer.
Instead, it utilized a switch that would be physically actuated by the lift when the lift was in the zero incline position. A revolution sensor counted lifted motor revolutions to determine subsequent lift positions. In addition two limit switches where used to remove power from the lift motor if the lift moved outside of its normal range.  When the unit was powered up the lift would start to hunt for the zero switches. It would first go up 4% (maximum lowest physical position was -3%) if it did not find the zero switch or it hit the upper limit switch, it would then go down until did find the zero switch. When the zero switch was located it would stop, the system would then know its physical position and be prepared to monitor the revolution sensor. If during this power up procedure the zero switch was not found an error 43 would be displayed.
Possible Causes
1. The lift position actuator does not physically operate the zero switch.
2. The lower PCA is bad.
3. The zero switch is bad.
Possible Remedies
1. There are several physical problems related to the lift platform mounting or the plate the zero switch is mounted on that can cause the actuator knob to miss the zero switch as it moves past. Repair the lift platform mounting, repair or replace the lift switch mounting plate as required.
2. The lower PCA provides a 5 VDC power source for the zero switch. You should measure 5 VDC across the zero switch when the zero switches activated. If the reading is significantly low, remove both wires from the zero switch and repeat the measurement across the wires removed from the zero switch. If the reading is still significantly low, verify the zero switch wiring. If the wiring is intact and correctly connected, replace the lower PCA.
3. Move the lift to position where the zero is switch is not activated and removes power from the treadmill. Remove both leads from the zero switch and measure the zero switch with an ohmmeter. The zero switch should read very near 0 ohms. While measuring the zero switch with the ohmmeter, activate the switch by hand, the reading should change to infinite (open).  If either of the above readings is significantly incorrect, replace the zero switch.

Error 44 - Un-commanded Lift Motion
Description:  The lift control system has detected that the lift is in motion without a lift command having been issued. This can happen in one of two ways: either the lift drive circuit has failed in a turned on condition or the lift position sensor (lift position potentiometer or revolution sensor) is sending an erroneous signal to the lift control circuit.
Possible Causes
1. Poor or intermittent connection in the lift position sensor.
2. Bad lift position sensor
3. Bad lower PCA.
Possible Remedies
1. This is the most common cause of an error 44. Verify all wiring and connections associated with the lift position potentiometer. Repair or replace wiring or connections as appropriate. Because of the nature of the revolution sensor an error 44 is rarely associated with it.
2. Operate the lift in the diagnostics while monitoring the lift position number being displayed. The the reading is erratic and makes large changes in readings the lift position potentiometer is probably bad. Replace the lift position potentiometer or the lift motor if it utilizes an internal potentiometer.
3. If there is actual lift motion without a manual or program control lift command having been issued, replace the lower PCA.

Error 45 - Lift Moving in Wrong Direction
Description:  The lift control system has detected that the lift is moving in the opposite direction of the issued lift command.
Possible Causes
1. Lift Motor hysterics.
2. Bad lower PCA
Possible Remedies
1. This error would typically happen when the lift was already in motion (typically downward) when a lift command in the opposite direction (lift up) was issued. Some motors exhibited a very long turn around time and the lift motor would still be moving in the original direction (downward) while the control system was attempting to move the lift in the opposite direction. If the error 45 conditions is persistent, replace the lift motor.
2. This is a very rare condition; if the lift moves in the opposite direction of the issued lift command, replace the lower PCA.

Error 50 - Too Much Brake (Magnet) Current
Description:  This error is associated with eddy current EFX’s. The resistance (brake) control system constantly monitors the amount of current being demanded by the eddy current magnet. Error 50 indicates that amount of current being demanded by the eddy current magnet is excessive.
Possible Causes
1. The most common cause of this error is shorted or damaged wiring between the lower PCA and the eddy current magnet.
2. The eddy current magnet is bad
3. The lower PCA is bad.
Possible Remedies
1. Carefully check the eddy current wiring and connections, ensure that the wires are not shorted together or shorted to the EFX frame. Repair or replace the damaged wiring as appropriate.
2. Remove the wires from the eddy current magnet. With an ohmmeter, measure across the eddy current magnets terminals. The ohmmeter should read approximately 100 ohms. If the reading is significantly low, replace the eddy current magnet. Measure between each eddy current magnet terminal and frame ground. Both readings should be infinite (open). If either reading is significantly low, replace the eddy current magnet.
3. If both the eddy current magnet wiring and the eddy current magnet are good (as tested above), replace the lower PCA.

 Error 53 - Can’t Read Target, Can’t Find Home Switch
Description:  This error is associated with the 5.17 EFX. When power is first applied to the 5.17, an arm with permanent magnets moves from its last position to the zero resistance position. Moving to the zero resistance position is a two-step process. First it must move forward far enough to actuate the home switch and the move rearward to a set position (zero resistance) by reading a
revolution sensor on the motor driving the moving arm. It detects the actual distance moved by counting motor revolutions. When in the correct physical positions the arm stops and the 5.17 is ready for use. If when moving forward the zero switch is not activated or when moving rearward a response is not seen from the revolution sensor, an error 53 will be displayed.
Possible Causes
1. The F2 fuse is blown.
2. Intermittent or damaged home switch wiring.
3. Intermittent or damaged gear motor wiring.
4. A bad home switch.
5. A bad gear motor.
6. A damaged gear motor target.
7. A bad lower PCA.
Possible Remedies
1. Remove power from the 5.17. Remove the F2 fuse from the lower PCA. Measure the fuse with an ohmmeter. The fuse should measure 1 ohm or less. If the reading is significantly high, replace the fuse. If the F2 fuse was blown there may have been a reason that will cause the fuse to blow again such as; damaged gear motor wiring or a bad gear motor. 
Carefully inspect the home switch wiring for intermittent or damaged wiring or connections. Replace or repair the wiring or connections as appropriate.
3. Carefully inspect the gear motor wiring for intermittent or damaged wiring or connections. Replace or repair the wiring or connections as appropriate.
4. With the moving arm away from the home switch, remove power from the 5.17. Remove both wires from the home switch. Check the home switch with an ohmmeter. It should measure approximately 0 ohms. While monitor the home switch resistance, activate the home switch by hand; the reading should change to infinite (open). If either reading is significantly incorrect, replace the home switch.
5. With power removed from the 5.17, remove both wires from the gear motor. Measure the gear motor resistance with an ohmmeter; it should read approximately 9 ohms. If the reading is significantly low or significantly high, replace the gear motor.
6. Visually inspect the gear motor target, if it is ripped, torn or badly scratched, replace the target.
7. Measure the voltage at the gear motor during the start up sequence, it should measure approximately 12 V.D.C. The voltage would only be present between the time the sequence was initiated and the error 53 is displayed.. If the voltage is significantly low or absent and the F2 fuse is good (see step 1), replace the lower PCA.

Error 54 - Target Pulses Lost During Operation
Description:  This error is associated with the 5.17 EFX. This error indicates that at some time after the initial start up sequence was successfully completed, the gear motor was instructed to move and no response was seen from the motors revolution sensor.
Possible Causes
1. The F2 fuse is blown
2. Damaged or Intermittent gear motor wiring.
3. Bad gear motor
4. Damaged gear motor target
5. Bad lower PCA
Possible Remedies
1.     Remove power from the 5.17. Remove the F2 fuse from the lower PCA. Measure the fuse with an ohmmeter. The fuse should measure 1 ohm or less. If the reading is significantly high, replace the fuse. If the F2 fuse was blown there may have been a reason that will cause the fuse to blow again such as; damaged gear motor wiring or a bad gear motor. 
2. Carefully inspect the gear motor wiring for intermittent or damaged wiring or connections. Replace or repair the wiring or connections as appropriate.
3. With power removed from the 5.17, remove both wires from the gear motor. Measure the gear motor resistance with an ohmmeter; it should read approximately 9 ohms. If the reading is significantly low or significantly high, replace the gear motor.
4. Visually inspect the gear motor target, if it is ripped, torn or badly scratched, replace the target.
5. Measure the voltage at the gear motor during the start up sequence, it should measure approximately 12 V.D.C. The voltage would only be present between the time the sequence was initiated and an error was displayed.. If the voltage is significantly low or absent and the F2 fuse is good (see step 1), replace the lower PCA.

Error 55 - Brake Home Switch Activated Unexpectedly
Description:  This error is associated with the 5.17 EFX. This error indicates that the home switch was activated at a time other than the initial start up sequence. The home switch is only used to initially position the moving arm immediately after the 5.17 has been powered up.
Possible Causes
1. Damaged or shorted home switch wiring.
2. Bad lower PCA.
Possible Remedies
1. Carefully check the home switch wiring for possible shorts or faults to the frame. Replace or repair the wiring as appropriate.
2. If the lower PCA is applying a constant 12 V.D.C. to the gear motor, replace the lower PCA.