Contn:
[3 of 5]
{00101010} Phase 1 - Rotor Fault.
Primary
Source
Action
- Turn off Smartdrive at the wall and back on again after 5 seconds.
Re-start.
{00101011} Phase 1 to 5 - OOB Switch Fault.
The
Motor Controller has found that the signal returning from the out of balance
switch indicates that the switch is permanently on or the harness to it is
isconnected.
Primary
Source - Mechanical
Action
Check
Smartdrive is level and that the bowl is not contacting the out of balance
lever.
Check
that the bias spring is correctly located between the wrapper and the outer
bowl.
Check
that the out of balance switch is free to move. Check switch operates correctly
when activated. Replace switch if suspect. If the out of balance switch shows
signs of corrosion replace the switch. Check the harness to the switch is
connected correctly. If the harness terminals show signs of corrosion, then fit
a new harness.
Check
the suspension is not catching.
Secondary
Source - Motor Controller. (Display Module Phase 1).
Action
- Replace Motor Controller. (Display Module Phase 1).
{00101100} Phase 2 to 5 - Water in Bowl During Spin.
The
Display has sensed a water level in the bowl during spin. This may be caused by
a slow pump out rate due to pump hose or pump partial blockage.
Primary
Source - Pump System
Action
Check
that the pump hose is not squashed or kinked.
Check
the length of the drain hose and try to reduce the length if excessively long.
A 1 metre extension hose of the same diameter fitted to the existing hose is
the maximum allowable length.
If
the bowl is empty of water, remove the pump from the pump housing and check
that it is not blocked. Also check that the drain hose is not blocked.
If
the bowl contains water, then service the pump from the top of Smartdrive by
removing the top deck and inner bowl. Bail out the water, remove the pump cap
and hood and clear the pump of any obstruction.
Check
that the water is not siphoning back into Smartdrive when the pump turns off
when the spin speed reaches 600 rpm.
Secondary
Source - Motor Controller
Action - Replace
Motor Controller.
{00101101} Phase 5 - Display Fault.
On
power up the display module has tested its ROM is corrupt.
Primary
Source - Display module
Action - Replace
Display module.
{00101110} Phase
5 IW - Display EEPROM Check.
The
Intuitive display has detected a problem with its internal EEPROM.
Primary
Source – IW Display module
Action - Replace
IW Display module.
{00101111} Phase
2 to 3 - Bowl Dis-engaged Fault.
While
carrying out a bowl check, the Motor Controller has found that the bowl is not
engaged even though the pressure sensor indicates that the bowl is empty. The
Motor Controller continues to check for 2 minutes. During this time the module
has not been able to determine a valid bowl status and so displays this fault.
This fault differs from fault 40 in that a valid bowl status could not be
determined. The first two areas to check are the clutch and the pressure tube.
If these two appear correct, then the fault could be with the pressure sensor
in the Motor Controller.
Primary
Source - Mechanical
Action
Check
that there are no clothes or other foreign objects preventing the clutch from
reengaging.
Next
check that the pressure tube has not come off and that it is not kinked.
Secondary
Source - Motor Controller.
Action
- Replace Motor Controller, if the above checks out without fault.
{00110000} Phase 2 to 5 - Hot and Cold Valve Fault.
The
Motor Controller has measured voltages from the valve diagnostic circuit that
indicate both the hot and cold valve are faulty. The most likely cause is that
the valve harnesses have not been connected correctly.
Primary
Source - Wiring
Action
- Check valve harnesses are correctly fastened to valves.
Secondary
Source - Water Valves
Action
- Check valve coils are not faulty ( open circuit ).
Tertiary
Source - Motor Controller
Action - The
valve drivers or valve diagnostic circuit may be at fault. If the primary and
secondary checks pass inspection then replace the Motor Controller.
{00110001} Phase 2 to 5 - Cold Valve Fault.
The
Motor Controller has measured a voltage from the valve diagnostic circuit that
indicates the cold valve is faulty. The most likely cause is that the valve
harness has not been connected correctly. See fault 48. for service procedure.
{00110010} Phase 2 to 5 - Hot Valve Fault.
The
Motor Controller has measured a voltage from the valve diagnostic circuit that
indicates that the hot valve is faulty. The most likely cause is that the valve
harness has not been connected correctly.
Primary
Source - Wiring
Action
- Check valve harnesses are correctly fastened to valves.
Secondary
Source - Water Valves
Action
- Check valve coils are not faulty ( open circuit ). If either of these
valves are low impedance it is likely that the Motor Control output has also
failed, in which case replace Motor Controller and valve(s).
NB. Phase 5 can give fault code 50 when Smartdrive
powers off while spinning. In this case there will be no fault.
Contd: