Contn:
[4 of 5]
{00110011} Phase 5 ECO – Recirculation Fault.
[4 of 5]
{00110011} Phase 5 ECO – Recirculation Fault.
The
product has detected that it is losing water during recirculation.
Primary
Source – Diverter Valve Wiring
Action
- Check diverter valve harness is correctly fastened to diverter valve.
Check flying lead in motor controller, and connection to valve next to drain
pump.
Secondary
Source – Diverter Valve
Action
- Check diverter valve resistance. If open circuit (nominal is 1500 ohms)
replace diverter valve. During recalculation, check that water is being recalculated
back into the bowl, and that no water is coming out of drain hose. If there is
some water coming from the drain hose, then the diverter valve could be faulty,
or it could be jammed with a foreign object.
Replace
diverter valve.
Tertiary
Source - Motor Controller
Action
- The diverter valve drive circuit may be at fault. If the primary and
secondary checks pass inspection then replace the Motor Controller.
{00110100}
Phase 5 ECO – Re-circulation Fault.
{00110011} Phase 2 to 5 - Rotor Position Sensor Fault.
The
Motor Controller has attempted a motor step test and has found that the motor
has not stepped to the correct position. It has detected that the motor is
connected and that the Motor Controller drive is operational. The Rotor
Position Sensor signal sensing system is at fault.
Primary
Source - Wiring
Action
- Check the Rotor Position Sensor harness for continuity and that the
connectors are correctly applied to the Rotor Position Sensor and to the Motor
Controller.
Secondary
Source - Rotor Position Sensor
Action
- Check Rotor Position Sensor with RPS Tester or Replace Rotor Position
Sensor.
Tertiary
Source - Motor Controller
Action
- The Motor Controller motor sensing circuitry may be faulty. Replace Motor
Controller.
{00110110} Phase 2 to 5 - Motor / Motor Control Step
Fail.
The
Motor Controller has attempted a motor step test and has found that the motor
has not stepped to the correct position. The Motor Controller has detected that
there is no motor current. This
indicates that either the motor is not connected or the Motor Controller motor
drive is faulty.
Primary
Source - Wiring
Action
- Check the continuity of the motor harness and that the connectors are
correctly applied to the stator and to the Motor Controller.
Secondary
Source - Motor
Action
- Check resistance of motor phases. Check the brass bridge terminal on the
stator is not open circuit or burnt. Otherwise replace stator.
Tertiary
Source - Motor Controller
Action
- Replace Motor Controller.
{00110111} Phase 3 to 5 - System Step Fail.
Primary
Source - Rotor Position Sensor
Action
Check
Motor & Rotor Position Sensor wiring
Check
Rotor Position Sensor with RPS tester.
{00111000} Phase 4 to 5 - Bowl Check Fault.
While
carrying out a bowl check Smartdrive has not been able to determine a valid
bowl status and so the Display flags this fault. This fault differs from fault
40 in that a valid bowl status could not be determined. The first two areas to
check are the clutch and the pressure tube.
Primary
Source - Mechanical
Action
Check
that there are no clothes or other foreign objects preventing the clutch from
reengaging.
Check
that the pressure tube has not come off and that it is not kinked.
Secondary
Source - Motor Controller (Phase 4). Rotor Position Sensor (Phase 5)
Action
- Replace Motor Controller(Phase 4). Rotor Position Sensor (Phase 5).
{00111001} Phase 4 to 5 – Motor Controller Fault.
The
Display module has requested the Motor Controller to perform an EEPROM write.
Prior to writing the Motor Controller has tested the 15 Volt supply and found
that it is below a safe level for writing EEPROM and has reported this to the
display. This may be due to mains transients at the time of write or due to a
faulty Motor Controller.
Primary
Source - Motor Controller
Action - Replace
Motor Controller.
{00111010} Phase 4 to 5 – Pressure Transducer Fault.
The
Pressure Transducer is outside normal limits.
Primary
Source - Motor Controller
Action
- Replace Motor Controller.
{00111011} Phase 4 to 5 - Display Module Fault.
The
Display module checked its physical ID on the display PCB and found it was out
of range.
Primary
Source - Display module
Action
- Replace Display module.
{00111100} Phase 4 to 5 - Motor Controller Fault.
On
power up the Motor Controller has tested its ROM against a known reference and
found differences.
Primary
Source - Motor Controller
Action
- Replace Motor Controller.
{00111101} Phase 4 - Motor Controller Fault.
The
Motor Controller has been attempting to perform an internal EEPROM write. Prior
to writing the Motor Controller has tested the 15 Volt supply and found that it
is below the safety level for writing EEPROM and has reported this to the
display. This may be due to mains transients at the time of write or due to a
faulty Motor Controller.
Primary
Source - Motor Controller
Action - Replace
Motor Controller.
{00111110} Phase 5 - Pump Fault.
The
Motor Controller has detected an excessive pump current.
Primary
Source- Pump
Action
- Replace Pump. NB. Just checking the resistance of the pump (approx. 33
ohms cold to 40 ohms hot) is NOT reliable as the pump inductance is also
important.
Secondary
Source - Motor Controller
Action - Replace
Motor Controller.
{00111111} Phase 5 – Motor Controller Fault.
The
Motor Controller has detected an internal communications problem between its
main control system and the pump control system.
Primary
Source - Motor Controller
Action - Replace
Motor Controller.
{01000000}
Phase 5 – Pressure Transducer Out of Range Error.
{01000001}
Phase 5 – Pressure Transducer Out of Range Error.
{01000010} Phase 5 – Pressure Transducer Out of Range
Error.
The
Motor Controller has received signals from the Pressure Transducer outside
normal values.
Primary
Source - Motor Controller
Action - Replace
Motor Controller.
{010xxxx} Phase 2 to 3 - Display / Motor Controller
Comms. Error.
Contd: